MININET communication

MININET communication is only supported on serial devices. Serial communication can be operated as a point-to-point connection (RS232) or as a network connection (RS485).

MININET is a master/slave protocol where the PVI MININET line carries out the functions of the master. A multi-master function is not possible via the MININET protocol.

PC requirements:

All necessary components are installed with PVI Setup.

The MININET line can be operated on the following platforms:

Windows platform

Limitations

Windows 7 or higher

-

Windows NT/2000/XP/Vista

No verification for Windows NT/2000 in PVI V4.0 or higher.

Requirements for SG2 controllers (MULTI/MIDI/MINI and Compact):

B&R standard software (model number: SWSPSCOM01-0 for 3.5")

Function blocks:

 

PLC mode

Hardware

 

Max. baud rate

DFMN.MSL

NETWORK ADAPTER MININET V0.01

 

 

 

DPMN.PRG

Mininet Driver NP02 / PP40

Network p. NP02

 

19200

DTMN.TAB

Configuration Table for DFMN

 

 

 

NDSA.MSL

MININET - SLAVE DRIVER A V2.40

PIFA/PIF1/PIF3

 

7200

NDSB.MSL

MININET - SLAVE DRIVER B V2.15

PP40/CP31/..

 

19200

NDSC.MSL

MININET - SLAVE DRIVER C V2.40

CP63/CP80/PP60

 

19200

NDSD.MSL

MININET - SLAVE DRIVER D V0.00

PRTS without FIFO

 

19200

NDSE.MSL

MININET - SLAVE DRIVER E V0.00

PRTS with FIFO

 

19200

NPLS.MSL

MININET - SLAVE PLC V2.04

 

 

 

MDSA.MSL

MININET/PLC - SLAVE A V2.30

PIFA/PIF1/PIF3

=NDSA + NPLS

7200

MDSB.MSL

MININET/PLC - SLAVE B V2.15

PP40/CP31/..

=NDSB + NPLS

19200

MDSC.MSL

MININET/PLC - SLAVE C V2.50

CP63/CP80/PP60

=NDSC + NPLS

19200

 

SPOIO mode

Hardware

 

Max. baud rate

NDSA.MSL

MININET - SLAVE DRIVER A V2.40

PIFA/PIF1/PIF3

 

7200

NDSB.MSL

MININET - SLAVE DRIVER B V2.15

PP40/CP31/..

 

19200

NDSC.MSL

MININET - SLAVE DRIVER C V2.40

CP63/CP80/PP60

 

19200

NDSD.MSL

MININET - SLAVE DRIVER D V0.00

PRTS without FIFO

 

19200

NDSE.MSL

MININET - SLAVE DRIVER E V0.00

PRTS with FIFO

 

19200

NSPO.MSL

MININET - SLAVE SPOIO PLC V2.04

 

 

 

MSSA.MSL

MININET/SPOIO - SLAVE A V2.41

PIFA/PIF1/PIF3

=NDSA + NSPO

7200

MSSB.MSL

MININET/SPOIO - SLAVE B V2.21

PP40/CP31/..

=NDSB + NSPO

19200

MSSC.MSL

MININET/SPOIO - SLAVE C V2.60

CP63/CP80/PP60

=NDSC + NSPO

19200

Requirements for SG3/SG4 controllers (System 2000):

PLC operating system V1.91 and higher

dvframe.br starting from V3.30 (included starting with PG2000 V2.39 / model no. 1A2000.01)

drv_mn.slb starting from V1.30 (model number: 1A2224.01)

RS485 network:

A maximum of 32 stations can be connected to a bus.

Executed as an RS485 twisted pair cable, shielded. Cross-section: min. 0.5 mm². Wave impedance: 120 ohms. Terminating resistor: 120 ohms on both ends. Length: maximum 1,200 meters. Maximum line resistance: 50 ohms per wire.

The cabling for the RS485 network can only be made using a bus structure. The bus connection can be made either directly or using a maximum 0,25 m long branch line.